Customization: | Available |
---|---|
After-sales Service: | Spare Parts, Technical Support, More Than 20 Years |
Warranty: | 1~4 Years |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model ESSW- | 03SC | 05SC | 08DC | 10DC | 12SC | 15TC | 20DC | 25DC | 30TC | 36TC | 40QC | 50QC | 60FC | ||
Technical Parameters |
Cooling Capacity | KW | 9.2 | 16.2 | 25.4 | 32.4 | 38.7 | 48.6 | 66.2 | 77.4 | 99.3 | 116.1 | 132.4 | 154.8 | 193.5 |
TR | 2.6 | 4.6 | 7.2 | 9.2 | 11.0 | 13.8 | 18.8 | 22.0 | 28.2 | 33.0 | 37.7 | 44.0 | 55.0 | ||
Rated Air Flow | m3/h | 1500 | 2500 | 4000 | 5100 | 6200 | 7800 | 10200 | 12600 | 15300 | 18000 | 20400 | 25500 | 30000 | |
External Static Pressure | Pa | 100 | 100 | 150 | 150 | 150 | 150 | 200 | 250 | 300 | 300 | 350 | 400 | 400 | |
Power Supply | 380/400/415V-3PH-50Hz | ||||||||||||||
Running Power | KW | 2.24 | 3.58 | 5.93 | 7.36 | 9.51 | 10.89 | 15.34 | 19.02 | 23.71 | 28.03 | 31.78 | 39.54 | 51.05 | |
Noise | dB(A) | ≤60 | ≤62 | ≤62 | ≤65 | ≤66 | ≤67 | ≤68 | ≤70 | ≤70 | ≤73 | ≤74 | ≤76 | ≤78 |
Items |
Unit | Water circulating quality | Supplementary water quality standard | ||
Standard values | Trend | ||||
Corrosion | Scaling | ||||
PH (25 ºC) | 6.5~8.0 | + | + | 6.0~8.0 | |
Electrical conductivity (25 ºC) | μS/cm | <800 | + | + | <200 |
Chloride ion Cl- | mg/L | <200 | + | <50 | |
Sulfate ions SO42- | mg/L | <200 | + | <50 | |
Acid consumption (PH4.8) | mg/L | <100 | + | <50 | |
Full hardness (CaCO3) | mg/L | <200 | + | <50 | |
Total iron (Fe) | mg/L | <1.0 | + | + | <0.3 |
Sulfide ion S2- | mg/L | Undetectable | + | Undetectable | |
Ammonium ion NH4 + | mg/L | <1.0 | + | <0.2 | |
Silicon dioxide SiO2 | mg/L | <50 | + | <30 |