Strong Air Flow Air Conditioning Vertical Exposed Fan Coil

Type: Fan Coil Unit
Air Tube Material: Galvanized Sheet
Corrosion Durability: Higher
Operating Voltage: 110V/220~240V-50Hz/60Hz-1pH
Noise Level: Low
Application Fields: HVAC
Customization:
Diamond Member Since 2015

Suppliers with verified business licenses

Rating: 5.0/5
Manufacturer/Factory & Trading Company

Basic Info.

Model NO.
EST800VE2
Mounting
Floor Standing
Lifetime
>20 years
Certification
CE, SGS, CCC
Condition
New
Color
Milk White
Pipe System
2 Pipe/4 Pipe
Air Outlet Static Pressure
0,12, 30PA
Air Outlet Way
Top
OEM/ODM
Available
Transport Package
Standard Export Packing, Such as Cartons
Specification
CE Approval
Trademark
Eurostars
Origin
Guangdong, Prc
HS Code
84159010
Production Capacity
10000 PCS/Year

Product Description

Strong Air Flow Air Conditioning Vertical Exposed Fan Coil 

1. Vertical exposed fan coil features:
(1)Low noise; (2) High efficient and energy saving; (3) Strong air flow; (4) Flexible installation; (5) Easy operation.

In central air conditioner system, Eurostars vertical exposed floor standing fan coil continuously exchanges the indoor air with cool & heat supplied by chiller system, in order to adjust the room temperature and humidity. Vertical floor standing fan coil is widely appliated in bureaux, business building, superstore, hotel, hospital, bank, apartment and amusement place.

2. Vertical floor standing fan coil unit nomenclature

ES  T   200    VE2      T     R    A    O   
1    2      3       4         5      6     7    8   
1: ES Eurostars
2 :T Terminal series
3 :200 Rated air flow: CFM
4 :VE2 Ceiling exposed floor mounted and the number of tube system
5 :T Coil type:  T-2C0H (Note: C-Cold water coil; H-Hot water coil)                                    
6 :R Connection pipe direction: R-Right (face to air outlet)  L-Left (face to air outlet)
7: A Power supply: A-220V-50HZ; K-208~230V-60HZ; N-115-60HZ; W-265~277V-60HZ
8 :O Sales region: O-Other regions;  C-Mainland China

3. Eurostars vertical exposed fan coil techinal specification
Please ask salesman for detailed complete data or visit our website:
eurostarschiller.en.made-in-china.com
Universal Exposed Fan Coil Unit(4 pipe system)
Model   EST 200HE4 300HE4 400HE4 500HE4 600HE4 800HE4 1000HE4 1200HE4 1400HE4
200VE4 300VE4 400VE4 500VE4 600VE4 800VE4 1000VE4 1200VE4 1400VE4
Power supply 220V/1PH/50HZ
Air flow
 (m3/h)
H 340 510 680 850 1020 1360 1700 2040 2380
M 260 390 510 640 770 1020 1280 1530 1790
L 170 260 340 430 510 680 850 1020 1190
Cooling capacity TH H W 1800 2700 3600 4500 5400 7200 9000 10800 12600
SH W 1368 2052 2736 3420 4103 5471 6839 8207 9575
TH M W 1494 2242 2989 3736 4483 5978 7472 8967 10461
SH W 1181 1771 2362 2952 3541 4722 5903 7084 8265
TH L W 1162 1744 2325 2906 3487 4649 5812 6974 8136
SH W 953 1430 1907 2383 2860 3813 4765 5718 6672
Heating capacity H W 1300 1940 2590 3240 3890 5180 6480 7780 9070
M W 1020 1530 2040 2550 3060 4070 5090 6110 7130
L W 820 1230 1630 2040 2450 3270 4080 4900 5720
 Noise  H dB(A) 37 39 41 43 45 46 48 50 51
Power input H W 37 52 62 76 96 134 152 189 228
Water flow
m³/h (H) 
Cooling pipe 0.31  0.46  0.62  0.77  0.93  1.23  1.54  1.85  2.16 
Heating pipe 0.11  0.17  0.22  0.28  0.34  0.45  0.56  0.67  0.78 
 Water resistance kPa Cooling pipe 16 18 20 23 28 30 33 37 40
Heating pipe 8 10 12 14 16 20 22 25 28
Pipe  Inlet water pipe ZG3/4" ZG3/4" ZG3/4" ZG3/4" ZG3/4" ZG3/4" ZG3/4" ZG3/4" ZG3/4"
Outlet water pipe ZG3/4" ZG3/4" ZG3/4" ZG3/4" ZG3/4" ZG3/4" ZG3/4" ZG3/4" ZG3/4"
Coil type  Hydrophilic aluminum fin arounds high efficient copper pipe 
Working pressure MPa 1.6
Condensation water pipe mm ¢16
Fan Type  Forward-pitched multi-wing centrifugal fan with double-suction impellers
 made from zinc-plated steel plates
Qty 1 2 2 2 2 4 4 4 4
Motor Type Single-phase capacitive motor equips with fine ball bearing, low noise and long service life
Qty 1 1 1 1 1 2 2 2 2
Note:
(1)Cooling: Inlet air temperature DB 27ºC,WB 19.5ºC; Chilled water inlet/outlet temp. 7ºC/12ºC.
(2)Heating: Inlet air temperature DB 21°C, heating water inlet temperature  60°C (tested by the same water flow with cooling condition).
(3)The noise level is measured in: background noise 11.5Db(A) semi-anechoic room as per GB/T19232-2003.
(4)Rated air flow is tested in standard air condition with DB 20ºC.
(5)Specifications are subject to product improvement and change without notice.

4. Vertical exposed fan coil unit correction factor
(1)Capacity correction factor at different condition:
Working Condition Hot water inlet temp.

Air inlet DB Temp. 40ºC 50ºC 60ºC 70ºC
Return air 17 ºC 0.58  0.82  1.11  1.40 
18 ºC 0.56  0.80  1.09  1.37 
19 ºC 0.54  0.77  1.06  1.34 
20 ºC 0.51  0.74  1.03  1.32 
21 ºC 0.48  0.71  1.00  1.29 
22 ºC 0.45  0.68  0.97  1.26 
23 ºC 0.42  0.65  0.94  1.23 
24 ºC 0.39  0.62  0.91  1.20 

(2)Cooling capacity correction factor:
Model EST 200HE2 300HE2 400HE2 500HE2 600HE2 800HE2 1000HE2 1200HE2 1400HE2
200VE2 300VE2 400VE2 500VE2 600VE2 800VE2 1000VE2 1200VE2 1400VE2
Medium Total Heat 0.83  0.83  0.83  0.83  0.83  0.83  0.83  0.83  0.83 
Low Total Heat 0.65  0.65  0.65  0.65  0.65  0.65  0.65  0.65  0.65 

(3)Heating capacity correction factor:
Model EST 200HE2 300HE2 400HE2 500HE2 600HE2 800HE2 1000HE2 1200HE2 1400HE2
200VE2 300VE2 400VE2 500VE2 600VE2 800VE2 1000VE2 1200VE2 1400VE2
Medium 0.79  0.79  0.79  0.79  0.79  0.79  0.79  0.79  0.79 
Low 0.62  0.62  0.62  0.62  0.62  0.62  0.62  0.62  0.62 
 
5.Vertical floor fan coil unit quotation remarks
(1)Packing: Standard export package
(2)Delivery Day: 10~25 working days after deposit is confirmed
(3)Delivery term: CIF,FOB or CNF EX-Work are welcomed
(4)Payment term: 30% deposit by TT, the balance will be paid by TT before delivery;
  Or 100% Irrevocable non-transferred LC at sight
(5)Warranty: 12~18 months after Bill of Lading date. Any unartificial failure occurred within the period, we'll supply you the spare parts for free, and permanent technical support & consultation all life long for the machines.
(6)Validity: 20 days
(7)Payment currency: USD

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now