Water Chiller Connected Cooling Water Air Handler Unit

Product Details
Customization: Available
Type: Air Handling Unit
Air Tube Material: Galvanized Sheet
Manufacturer/Factory & Trading Company

360° Virtual Tour

Diamond Member Since 2015

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Terms of Payment
LC, T/T
OEM/ODM Availability
Yes
Find Similar Products

Basic Info.

Model NO.
EST
Operating Voltage
380/400 VAC
Noise Level
Low
Application Fields
HVAC
Mounting
Ceiling Mount
Lifetime
>20 years
Certification
CE
Condition
New
Ahu Panel Color
Bule/White Panel
Power Supply
230/440/460V-3pH-60Hz Zvailable
Fan
Deton,Nicotra
Motor
Jishaneg,Siemens
Heat Exchanger
High Efficiecny Fin Type
Controller
Optional
Transport Package
Standard Package
Specification
CE
Trademark
Eurostars
Origin
Guangdong, Prc
HS Code
8415909000
Production Capacity
2000PCS/Year

Product Description

1.Selling Point-Eurostars chilled water fan coil-air handling unit
a)Low Noise
b)Efficient and Energy Saving
c)Easy Operation and Installation
d)Compact Exterior
e)High quality
f)Competitive price
 
2.Product series-Eurostars chilled water fan coil-air handling unit
-Horizontal ceiling ducted air handling unit
-Horizontal concealed air handling unit
-Vertical concealed air handling unit
-Vertical exposed air handling unit
-Modulus Air Handling Unit-multi-function air handling unit
 
3.Unit specification-air handling unit
Following is only one part of our whole air handling unit specification,please ask Eurostars salesman for other detailed specification.
Heat exchanger:4Rows
Model Air Flow Volume Motor-external Linked  Return Air
Rated Air Flow Air Flow Range Pressure Power Input Cooling Capacity Heating Capacity Water Flow Water Resistance Water inlet/outlet pipe Diameter
*1000CMH Pa kW kW L/min kPa DN
EST2HC4 2 1.7~2.2 150 0.55 11.44 18.41 34.5 3 32
EST3HC4 3 2.2~3.4 200 0.75 13.89 22.36 41.9 3.5 32
EST4HC4 4 3.4~4.4 250 1.1 20.63 33.21 62.2 4.7 40
EST5HC4 5 4.4~5.4 250 1.5 25.74 41.44 77.6 6.2 40
EST6HC4 6 5.4~6.7 300 2.2 30.91 49.76 93.2 8.5 40
EST8HC4 8 6.7~8.7 300 2.2 41.26 66.42 124.4 10.5 50
EST10HC4 10 8.7~10.8 350 3 51.61 83.09 155.6 14.5 50
EST12HC4 12 10.8~13 350 4 62.12 100.01 187.3 15.1 50
EST15HC4 15 13~15.4 400 5.5 73.87 118.93 222.7 15.8 65
EST16HC4 16 15.4~16.8 400 5.5 79.61 128.17 240 16.2 65
EST18HC4 18 16.8~18.8 400 7.5 91.05 146.59 274.5 16.4 65
EST20HC4 20 18.8~21.5 500 2*4 103.6 166.79 309 16.6 65
EST24HC4 24 21.5~25.5 500 2*5.5 130 209.3 387.8 16.8 2*65
EST27HC4 27 25.5~28.5 500 2*5.5 149.8 241.17 446.8 17.5 2*65
EST30HC4 30 28.5~31 500 2*7.5 169.6 273.05 505.9 18.3 2*65
EST32HC4 32 31~32.8 500 2*7.5 183.9 296.07 548.5 18.7 2*65
EST34HC4 34 32.8~34.8 550 2*7.5 195.8 315.23 584 19.1 2*65
EST36HC4 36 34.8~37.5 550 2*7.5 206.9 333.1 617.3 19.4 2*65
EST40HC4 40 37.5~42 600 2*11 230.8 371.58 681.5 20.2 2*65
EST45HC4 45 42~47 600 2*11 259 416.99 764.5 22.2 2*65
EST50HC4 50 47~52 650 2*11 287.2 462.39 848.1 25 2*65
EST55HC4 55 52~57 650 2*11 316.2 509.08 933.7 28.3 2*65
EST60HC4 60 57~64.5 700 2*15 345.4 556.09 1020 31.7 2*65
EST70HC4 70 64.5~75 700 2*15 402.4 647.86 1188 38.4 2*80

Heat exchangers:6Rows
Model Air Flow Volume Motor-external Linked  Return Air
Rated Air Flow Air Flow Range Pressure Power Input Cooling Capacity Heating Capacity Water Flow Water Resistance Water inlet/outlet pipe Diameter
*1000CMH Pa kW kW L/min kPa DN
EST2HC6 2 1.7~2.2 150 0.55 15.4 24.79 46.5 3.8 32
EST3HC6 3 2.2~3.4 200 0.75 18.7 30.1 56.5 4.4 32
EST4HC6 4 3.4~4.4 250 1.1 27.8 44.75 83.9 6 40
EST5HC6 5 4.4~5.4 250 1.5 34.7 55.86 104.7 7.9 40
EST6HC6 6 5.4~6.7 300 2.2 41.7 67.13 125.8 10.8 40
EST8HC6 8 6.7~8.7 300 2.2 55.7 89.67 167.9 13.4 50
EST10HC6 10 8.7~10.8 350 3 69.7 112.21 210 18.5 50
EST12HC6 12 10.8~13 400 4 83.9 135.07 252.8 19.2 65
EST15HC6 15 13~15.4 400 5.5 99.7 160.51 300.6 20.1 65
EST16HC6 16 15.4~16.8 400 5.5 107.5 173.07 324 20.7 65
EST18HC6 18 16.8~18.8 400 7.5 122.9 197.86 370.5 20.9 65
EST20HC6 20 18.8~21.5 500 2*4 139.8 225.07 417.1 21.2 65
EST24HC6 24 21.5~25.5 500 2*5.5 175.5 282.55 523.5 21.4 2*65
EST27HC6 27 25.5~28.5 500 2*5.5 202.2 325.54 603.1 22.3 2*65
EST30HC6 30 28.5~31 500 2*7.5 228.9 368.52 682.9 23.3 2*65
EST32HC6 32 31~32.8 500 2*7.5 248.2 399.6 740.4 23.9 2*65
EST34HC6 34 32.8~34.8 550 2*7.5 264.3 425.52 788.4 24.4 2*65
EST36HC6 36 34.8~37.5 550 2*7.5 279.3 449.67 833.3 24.7 2*65
EST40HC6 40 37.5~42 600 2*11 311.6 501.67 920 25.8 2*65
EST45HC6 45 42~47 600 2*11 349.6 562.85 1032.2 28.3 2*65
EST50HC6 50 47~52 650 2*11 387.8 624.35 1144.9 31.9 2*65
EST55HC6 55 52~57 650 2*11 426.9 687.3 1260.4 36.1 2*80
EST60HC6 60 57~64.5 700 2*15 466.3 750.74 1376.7 40.5 2*80
EST70HC6 70 64.5~75 700 2*15 534.2 874.5 1603.8 49 2*80

Heat exchangers:8Rows
Model Air Flow Volume Motor-external Linked  Return Air
Rated Air Flow Air Flow Range Pressure Power Input Cooling Capacity Heating Capacity Water Flow Water Resistance Water inlet/outlet pipe Diameter
*1000CMH Pa kW kW L/min kPa DN
EST2HC8 2 1.7~2.2 150 0.55 19.43 31.28 58.6 4.6 32
EST3HC8 3 2.2~3.4 200 0.75 23.61 38.01 71.2 5.4 32
EST4HC8 4 3.4~4.4 250 1.1 35.06 56.44 105.7 7.3 40
EST5HC8 5 4.4~5.4 250 1.5 43.75 70.43 131.9 9.7 40
EST6HC8 6 5.4~6.7 300 2.2 52.54 84.58 158.4 13.2 50
EST8HC8 8 6.7~8.7 300 2.2 70.12 112.89 211.4 16.4 50
EST10HC8 10 8.7~10.8 350 3 87.73 141.24 264.5 22.6 50
EST12HC8 12 10.8~13 350 4 105.61 170.03 318.4 23.6 65
EST15HC8 15 13~15.4 400 5.5 125.55 202.13 378.5 24.7 65
EST16HC8 16 15.4~16.8 400 5.5 135.33 217.88 408 25.3 65
EST18HC8 18 16.8~18.8 400 7.5 154.77 249.17 466.6 25.6 65
EST20HC8 20 18.8~21.5 500 2*4 174.24 280.52 525.3 25.9 65
EST24HC8 24 21.5~25.5 500 2*5.5 218.66 352.04 659.2 26.2 2*65
EST27HC8 27 25.5~28.5 500 2*5.5 251.93 405.6 759.5 27.3 2*65
EST30HC8 30 28.5~31 500 2*7.5 285.26 459.26 860 28.6 2*65
EST32HC8 32 31~32.8 500 2*7.5 309.28 497.94 932.4 29.2 2*65
EST34HC8 34 32.8~34.8 550 2*7.5 329.32 530.2 992.8 29.8 2*65
EST36HC8 36 34.8~37.5 550 2*7.5 348.09 560.42 1049.4 30.3 2*65
EST40HC8 40 37.5~42 600 2*11 384.28 618.69 1158.5 31.6 2*65
EST45HC8 45 42~47 600 2*11 431.15 694.15 1299.8 34.7 2*65
EST50HC8 50 47~52 650 2*11 478.22 769.93 1441.7 39.1 2*65
EST55HC8 55 52~57 650 2*11 523.5 842.83 1578.2 44.2 2.*80
EST60HC8 60 57~64.5 700 2*15 575.04 925.81 1733.6 49.5 2*80
EST70HC8 70 64.5~75 700 2*15 669.91 1078.55 2019.6 60 2*100

4.Eurostars Quotation Remarks-Air handling unit
1.Packing: Standard export package
2.Delivery Day: 15~20 working days after deposit is confirmed
3.Delivery term: CIF,FOB or CNF EX-Work are welcomed
4.Payment term: 30% deposit by TT, the balance will be paid by TT before delivery;
  Or 100% Irrevocable non-transferred LC at sight
5.Warranty: 12~18 months after Bill of Lading date. Any unartificial failure occurred within the period, we'll supply you the spare parts for free, and permanent technical support & consultation all life long for the machines.
6.Validity: 20 days
7.Payment currency: USD
 
5.CERTIFICATE-- CE certificated