Evaporator Unit for Freezer with High Quality Est-7.7kt

Product Details
Customization: Available
Cooling Method: Indirect Cooling
Certification: CE
Manufacturer/Factory & Trading Company

360° Virtual Tour

Diamond Member Since 2015

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Terms of Payment
LC, T/T
OEM/ODM Availability
Yes
Find Similar Products

Basic Info.

Model NO.
EST-7.7KT
Condition
New
Power Supply
380V-50Hz,Others Are Optional
OEM
Available
Ss Casing
Optional
Coil
with Bule Fins
Transport Package
Standard Export Package
Specification
CE
Trademark
EUROSTARS
Origin
China
HS Code
8418692090
Production Capacity
5000PCS/Year

Product Description


1.General Introduction -air cooler or evaporator for cold storage or cold room
EST series bilateral air exhaust air cooler is a cooling system, widely application in food processing room with evenly air blowing from bilateral.It is divided into two series according to different room temperature:
JT for 0ºC room temperature
KT for -18ºC room temperature
 
2.Unit Features-air cooler or evaporator
(1) Delicate spray plastic coating casing, optional for aluminum magnesium alloy or stainless steel plate. 
(2) High efficient heat exchanger with staggered internal thread copper tubes.
(3)Outer rotor motor, bilateral air blows, low sound level. 
(4)Exquisite stainless steel electric heating tubes are spread evenly with coils to assure the excellent defrosting.
 
3.Detailed Parameter-air cooler or evaporator
Bilateral Air Exhaust Air Cooler 
Fin Distance: 4.0 mm
Model Capacity Area Pipe Volume Fan Electrical Defrost
Air Flow Diameter Power Voltage Power Voltage
kw dm³ m³/h mm w v kw v
EST-5.5JT 5.5 22.8 2.5 4000 400 1*250 380 0.8 220
EST-7.3JT 7.3 30.4 3.4 4000 400 1*250 380 1.2 220
EST-10.1JT 10.1 42.0  4.4 8000 400 2*250 380 1.4 220
EST-13.5JT 13.5 56.1  5.9 8000 400 2*250 380 1.6 220
EST-16.8JT 16.8 70.0  7.2 12000 400 3*250 380 2.4 220
EST-21.0JT 21.0  87.6 8.9 12000 400 3*250 380 3.6 220
EST-28.0JT 28.0  116.8 11.7 16000 400 4*250 380 4.8 220
EST-33.6JT 33.6 140.2 14.0  16000 400 4*250 380 6.4 220
Remarks:
Note: Test Conditon: Room Temperature: 2ºC,Temperature Difference:8ºC;

Fin Distance: 6.0 mm
Model Capacity Area Pipe Volume Fan Electrical Defrost
Air Flow Diameter Power Voltage Power Voltage
kw dm³ m³/h mm w v kw v
EST-3.1KT 3.1 15.6 2.5 4000 400 1*250 380 1.6 220
EST-4.1KT 4.1 20.8 3.4 4000 400 1*250 380 1.8 220
EST-5.8KT 5.8 28.8  4.4 8000 400 2*250 380 2.8 220
EST-7.7KT 7.7 38.4  5.9 8000 400 2*250 380 3.2 220
EST-9.6KT 9.6 48.0  7.2 12000 400 3*250 380 3.6 220
EST-12.0KT 12.0  60.0  9.5 12000 400 3*250 380 4.8 220
EST-16.0KT 16.0  80.0  10.6 16000 400 4*250 380 6.4 220
EST-19.2KT 19.2 96.0  14.0  16000 400 4*250 380 8.0  220
Remarks:
Note: Test Conditon: Room Temperature: -18ºC,Temperature Difference:8ºC;

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier