Low Noise Water Cooled Screw Water Chiller/Water Source Heat Pump

Energy Efficiency Grade: a Class
Heat Temperature: 50-70°C
Work Environment: Common Heat Pump
Heat Source: Water-source
Heating Type: Circulating Heat
Application: Villa Family, Sauna and Swimming Pool, Hotels, Factory Hospital, Student Apartments, Beauty Salons
Customization:
Diamond Member Since 2015

Suppliers with verified business licenses

Rating: 5.0/5
Manufacturer/Factory & Trading Company

Basic Info.

Model NO.
ESGW025SOHN
Certification
CE, CCC, SGS
Heat Pump Compresor
Taiwan Hanbell
Heat Pump Expansion Valve
Emerson
Heat Pump Dry Filter
Danfoss
Optional
Partial Heat Recovery
Compressor Quantity
1 or 2
Transport Package
Standard Export Package
Specification
CE
Trademark
Eurostars
Origin
Guangdong, Prc
HS Code
8418692090
Production Capacity
200 PCS/Year

Product Description

Low Noise Water Cooled Screw Water Chiller/Water Source Heat Pump

1.Brief introduction-Eurostars water cooled chiller water source heat pump
a)Underground water source
b)Intellectualized control system and low noise
c)High efficient and energy saving
d)Easy operation and installation
e)Compact exterior
f)High quality
g)Competitive price
 
2.Unit Features-Eurostars water cooled water chiller water source heat pump
1).Heating capacity ranged from 105Kw to 3407 Kw.
2). Adopt good quality famous brand Hanbell screw compressor,high efficiency, low noise, less wearing and long life
3).Both Evaporator and Condenser are high quality and high efficiency
4). World famous brand parts: such Emerson expansion valve, FUJI contactor other brand like PUNP, Schneider.
5). Can be widely used in different area,such as Massage center, Hospital, Hotel, School, etc 
6). Strong unit base frame ensured the equipment stable operation 
7). Adopt leading brand PLC or SCM controller
8). Multi-capacity regulation, energy saving, cost cut down greatly for operation and maintenance.
 
3.Technical parameter-water cooled water source heat pump
Please ask salesman for detailed complete data 
or visit our website: eurostarschiller.en.made-in-china.com
Screw-type Water Source Heat Pump (one compressor)
Model   ESGW025SOHN035SOHN045SOHN065SOHN070SOHN085SOHN095SOHN105SOHN115SOHN135SOHN
Rated Cooling
Capacity
Cooling Capacity (KW) 105140182249272321372406437519
Cooling Capacity (USRT) 29.86 39.82 51.76 70.82 77.36 91.30 105.80 115.47 124.29 147.61 
Input Power (KW)18.924.830.741.946.051.259.865.471.683.0
Rated Heating CapacityHeating Capacity (KW)126168215293320374433472512603
Heating Capacity (USRT)35.84 47.78 61.15 83.33 91.01 106.37 123.15 134.24 145.62 171.50 
Input Power (KW)26.735.0 43.158.964.671.583.591.3100.1115.9
RefrigerantR407C
CompressorSemi-hermetic  Screw Type  
Power Supply 3φ-380V-50HZ
Safety ProtectionPhase reversion protection, Phase lack protection, Overload current protection,
Discharge air temp.  protection, Low & High pressure protection,
Low temp.  protection, Reserved water flow protection interface.
Number of Refrigeration Circuit1
Capacity Control (%)0,66,1000,50,75,100
Refrigerant Charge (Kg)17243040445259657186
Chilled WaterTemp of inlet/outlet water12ºC/7ºC
Water Side Max Pressure (MPa)
Dia.of Pipe  (inch) 2"2-1/2"3"3"3"3"4"4"4"4"
Water Flow (m3/h)18.1 24.1 31.3 42.8 46.8 55.2 64.0 69.8 75.2 89.3 
Pressure drop (kPa) 20252932415055605839
Underground
water
Temp of inlet/outlet water18ºC/29ºC
Water Side Max Pressure (MPa)1
Dia.of Pipe  (inch) 2"2-1/2"3"3"3"3"4"4"4"5"
Water Flow (m3/h)9.913.116.822.92529.233.836.94047.1
Pressure drop (kPa) 37434148484745464647
Running Noise dB(A)73.173.774.875.075.079.680.481.583.184.2
Total weight (Kg)88091010801220139015101620172018302140
Running Weight (Kg)970101012201380153016701780187020202400
Dimension L×W×HDetailed dimensions are according to the actual finished product sizes.

Screw-type Water Source Heat Pump (one compressor)
Model   ESGW155SOHN165SOHN175SOHN205SOHN225SOHN240SOHN265SOHN335SOHN395SOHN440SOHN
Rated Cooling
Capacity
Cooling Capacity (KW) 6056456747858629251033129715271703
Cooling Capacity (USRT) 172.07 183.45 191.70 223.27 245.16 263.08 293.80 368.89 434.30 484.36 
Input Power (KW)97.5103.4108.9125.3137.7146.7163.6206.3241.6267.0
Rated Heating CapacityHeating Capacity (KW)705751786913100210741198150617711972
Heating Capacity (USRT)200.51 213.59 223.55 259.67 284.98 305.46 340.73 428.33 503.70 560.86 
Input Power (KW)136.1144.3152.1175.1192.3204.9228.6288.2337.5372.9
RefrigerantR407C
CompressorSemi-hermetic  Screw Type  
Power Supply 3φ-380V-50HZ
Safety ProtectionPhase reversion protection, Phase lack protection, Overload current protection,
Discharge air temp.  protection, Low & High pressure protection,
Low temp.  protection, Reserved water flow protection interface.
Number of Refrigeration Circuit1
Capacity Control (%)0,50,75,100
Refrigerant Charge (Kg)97105109127141150168207243277
Chilled WaterTemp of inlet/outlet water12ºC/7ºC
Water Side Max Pressure (MPa)
Dia.of Pipe  (inch) 5"5"5"5"5"5"5"8"8"8"
Water Flow (m3/h)104.1 110.9 115.9 135.0 148.3 159.1 177.7 223.1 262.6 292.9 
Pressure drop (kPa) 43577236536365676972
Underground
water
Temp of inlet/outlet water18ºC/29ºC
Water Side Max Pressure (MPa)1
Dia.of Pipe  (inch) 5"5"5"5"5"5"6"6"8"8"
Water Flow (m3/h)55.158.761.471.478.38493.7117.7138.5154.1
Pressure drop (kPa) 46475359616265677681
Running Noise dB(A)86.386.686.987.187.387.688.490.390.891.2
Total weight (Kg)2270246025402680290030603310374039804300
Running Weight (Kg)2520272029203060338036003830426045204840
Dimension L×W×H Detailed dimensions are according to the actual finished product sizes.

(1).Rated Cooling Capacity Based on: Underground water in/outlet temp 18ºC/29ºC;Chilled water in/outlet temp. 12ºC/7ºC,  Fouling factor: 0.088.°C/KW.
(2).Rated heating capacity based on:Underground water inlet temp. 15°C;Hhot water inlet temp. 40°C.

4.Eurostars water cooled water source heat pump water chiller protection devices
1)Phase reversion protection, 
2)Overload current protection,
4)Phase lack protection, 
5)Discharge air temp. protection, 
6)Low&High pressure protection, 
7)Reserved water flow protection interface,
8)Low temp. protection.

5.Eurostars water source heat pump chiller series
-Commercial Water Source Heat Pump Chiller
-Scroll type water cooled water source heat pump
-Screw type water cooled water source heat pump
-Flooded type water cooled water source heat pump
 
-Commercial Air Cooled Heat Pump Chiller
-Scroll type air cooled air source heat pump
-Screw type air cooled air source heat pump
 
-Cooling&Heating&Sanitay hot water
-Air source heat pump with heat recovery
-Water source heat pump with heat recovery

Send your message to this supplier

*From:
*To:
avatar Mr. John
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now